Estimated Lead Time: 8-10 Weeks
-
Manufacturer: Allen-Bradley
-
Motor Protection Circuit Protectors
-
With integrated auxiliary switch : No
-
With integrated under voltage release : No
-
Rated short-circuit breaking capacity lcu at 400 V, AC : 70 kA
-
Rated permanent current Iu : 150 A
-
Rated operating voltage : 690 A
-
Type of control element : Other
-
Overload release current setting : 60 A
-
Type of electrical connection of main circuit : Screw-/spring clamp connection
-
Rated motor current : 150 A
-
Insulation voltage (Ui) : Rated 1000V per IEC
-
Electrical life cycle : 8000 @ 415V AC
-
Adjustable rated motor current : I1 = 0.4...1 x In (60...150 A)
-
Trip class : Class 3E, 5E, 10E, 20E (approx. 2...20 s)
-
Voltage for reverse-fed circuit breaker, max : 600V AC max. per UL/CSA, 600V AC max. per IEC
-
Rated ultimate short-circuit breaking capacity (Icu) : IEC 60947-2: 70 kA @ 500V DC, 3 poles in series
-
Rated service short-circuit breaking capacity (Ics) : IEC 60947-2: 100% @ 690V AC
-
Interrupting rating : NEMA, UL 489, CSA C22.2 no. 5: 65 kA @ 480V AC, 50/60 Hz
-
Instantaneous current : Adjustable from 6...13 x In (150 A maximum rated motor current)
-
Number of poles : 3
-
With thermal protection : Yes
-
Phase failure sensitive : Yes
-
Switch off technique : Thermomagnetic
-
Rated impulse voltage withstand (Uimp) : 8 kV
-
Control element : Toggle
-
Unbalace detection (50 % of I1) : ON or OFF
-
Interrupting rating/breaking capacity : High break
-
Width : 4.13 mm
-
Depth : 82.5 mm
-
Height : 6.3 mm
-
Frame size : 250 A
-
Device construction : Built-in device fixed built-in technique
-
Degree of protection (IP) : IP20
-
Mechanical life operations : 25000 /h
-
Protection type : Thermal/magnetic- adjustable thermal/fixed magnetic TMD
-
Factory option : Shunt open release, 110...120V AC/DC
-
Wire temperature rating : Al or Cu 75 °C
-
Operating temperature : -13 °F
-
Storage temperature : -40 °F
-
Ambient temperature without derating : 104 °F [40 °C]
-
Weight : 2.4 Kg
-